Product Description
Eaton K1600-LV-VSR Vacu-Breaker Starter Replacement 425A 600V 200KA FusedK1600LVVSR-UA-YAG
kr.05222023.19
- Rated Maximum Volts 600V
- Maximum HP@480V 300HP
- Contactor Amps 540A
- Maximum Fuse Rating 600A
- Fused Short Circuit Rating 200kA
- Maximum Continuous 425A
- TYPE: K1600-LV-VSR
- STYLE: 94M5052G12
- WEIGHT: 165LB
- SER NO. LVVSR14020010
- I.B. IB02709151E
- CLOSE CURRENT: 11.6A
- VOLTAGE RANGE 100-140VDC
- TRIP UNIT 1.2A
- VOLTAGE RANGE 70-104VDC
- G.O. NO. IBRSSR8591-1
- CURRENT TRANSFORMER
- RATIO 600:5A
- CAT. 531-601
- RF 1.33
- ACC CLASS 0.3 B0.2
- 50-400HZ 600V INS CLASS 10KV
- FUSE TYPE
- FERRAZ SHAMUT AMP-TRAP 2000
- AJT600EI
- 600A
- 600V
- 500VDC
An excellent tool for starting Low Voltage class motors is a new line-up of fused vacuum contactors, but this requires an outage, new equipment, new cables, changes in the power switchgear coordination and often a loss of drawout and metal-enclosed switchgear features. To get the best of both types of apparatus, a combination, or hybrid, of a power circuit breaker and a vacuum contactor is a better solution. The hybrid device is a vacuum starter replacement (VSR) with the following features:
• Drawout capability
• Utilizes the same cell interface components for levering and interlocking
• Minimum cell modifications
• Current limiting fuses as primary fault protection
• Hundreds of thousands of switching operations
• Compatibility and testing to IEEE/ANSI C37.59, C37.13.1
Product Videos
Custom Field
Breaker Amps 425
Breaker Volts 425
Breaker Poles 3
Breaker AIC 200
Bin Location S-1-1-2