Product Description
LSN Dual Lite LSN D120-02S-120 D Series Lighting Inverter 1kA 20A 120V 1PhISN
LIFE SAFETY NETWORK
Man Date: 6-1-2015
Section 100 System Installation Instructions
101 Specifications
Input
"Input voltage: 120, 208, 240, 277or 347VAC +10-15%.
Input frequency: 60Hz ‡3%
Synchronizing slew rate: 1 Hz per second nominal
• Input lightning protection: Meets ANSI 62.41, UL 924 and UL 1778 requirements
Single Phase
Output voltage: 120, 240, 277, 240/120, 277/120 or 347VAC.
Output regulation: (static) #5% based on a 5% - 100% resistive load
- Minimum loading: none required.
Output distortion: Less than 5% THD linear load
Load power factor: 75 lag to .8 lead
Output frequency: Normally, synchronized to utility, +.05 Hz during emergency - Overload: 150% momentary, 120% for five minutes, 110% for ten minutes